MAXIMUM
REPETITIVE SELF RESET SURGE:
3500Volts,1750 Amps for 100 pulses using 2V
source.
per: EN61000-4-5 Specification.
*MAXIMUM FAIL SAFE SURGE:
4000 Volts 2000 Amps for 100 pulses
using 2V source.
per EN61000-4-5 Specification. Exceeds EN6100-4-5, level 4.
CLAMPING VOLTAGES:
Common Mode - Line to Line
Differential Mode - Line to Ground
*CAPACITANCE:
Line/Line: <40pF
Line/Ground: <40pF
COMPONENT RESPONSE TIME:
Less than 10 Nanoseconds
OPERATING TEMPERTURE:
(-40șC TO +85șC)
PART NUMBER SELECTION:
Format:
DB-(connector type 9, 15, 25, 36,
37 etc.)-(clamp voltage)
Example: DB-25-18
|
APPLICATION |
MODEL |
MAX OPERATING
VOLTAGE |
CLAMP VOLTAGE |
|
RS422,
RS423,RS485 |
DB(_)-7 |
5.5V |
07V |
|
RS232, DIGITAL
CURRENT LOOP |
DB(_)-18 |
16.0V |
18V |
|
ANALOG CURRENT
LOOP |
DB(_)-27 |
25.5V |
27V |
OPERATION:
The Zap-Tech protector will repetitively protect
and reset without
degradation up to it's maximum repetitive self-reset surge.
If it is
subjected to more than it's maximum repetitive
self-reset surge, the
device will remain in a clamped mode indicating that it should be removed
or replaced while keeping the equipment
safe from subsequent surges.
INSTALLATION:
Zap-Tech protectors should be installed in series with the incoming
communication line at the port of the equipment being protected. The
protector's connector shell must be connected to the chassis ground
of the protected equipment.
IMPORTANT!
It is important that the protector and the chassis of the equipment to be
protected are both properly grounded to a properly earthed electrical
safety ground via the equipment's 3-prong power cord and/or a ground
wire of 14 AWG or larger. Protectors should be installed at both ends of
communication lines to ensure equipment protection at each end.
© Copyright
2001 Zap-Tech Corporation all rights reserved.
|
|
CONTACT FACTORY FOR
SPECIFIC DETAILS
PROTECTORS FOR SUBMINIATURE D (DB) (DSUB)
INTERFACES:
DB9 SERIES
D15 SERIES
DB15HD SERIES
DB25 SERIES
DB37 SERIES
DB50 SERIES
PROTECTORS FOR CENTRONIC "CHAMP" STYLE
INTERFACES :
14 POSITION
24 POSITION
36 POSITION
50 POS (RJ21)
PROTECTORS FOR RIBBON CABLE CONNECTOR INTERFACES:
PLEASE SPECIFY
RIBBON TYPE, CONNECTOR PIN QUANTITY,
AND GRID CENTERS:
Example:
0 .050 ribbon, 20 contact, 2 rows, 0.100 centers0>
Custom
variations are available including mixed or
special voltages, different connectors or pin outs.
Contact your supplier for details.

P.O. BOX 17078
RENO, NV, USA 89511
888-727-1951 Fx:
775-227-7722 www.zap-tech.com
*Applies
to all units except 62V and 260V Devices.
All specifications are subject to change without
notice.